Supermarket freezer hacks: four design decisions product teams should revisit

Share:

⏩ TL;DR

Between October and early November 2026, attackers took over commercial refrigeration controllers in hundreds of European supermarkets (CERT-FR, 2026) and changed their settings, in some cases reportedly to temperatures as high as 50°C (Infosecurity Magazine, 2026). Research published in August found that both product families let an attacker work out a valid admin login, one from the date and the other from the date and the device's MAC address (Claroty Team82, 2026). Fixes for those flaws were out before the first wave, but France's cyber agency says the October attacks didn't need them: the controllers were reachable from the internet and protected by weak passwords (Le Monde Informatique, 2026). If you design connected equipment, your team makes the same decisions. 

Table of Contents

What happened to Europe's supermarket freezers?

The first wave of cyberattacks hit France on 11th and 12th October. The French government later put the number of affected supermarkets at around 700 (IT-Connect, 2026). France’s national CERT named the compromised equipment as Danfoss AK-SM and AK-SC system managers and Copeland and Dixell XWEB supervisors (CERT-FR, 2026).

A second wave followed overnight on 1st-2nd November, when chains in at least seven countries, including Belgium and Sweden, found their freezers warming before opening time (Silicon UK, 2026). Several UK meat processors were also hit. The National Cyber Security Centre (NCSC) said it was working with them and called the national impact minimal (ITV News, 2026).

In a separate attack on equipment from another supplier, Coolworld, cold storage rooms at France’s national blood service (EFS) were reportedly turned to 110°C (Infosecurity Magazine, 2026).

 

The UK had a narrower escape. In late October, a consultant at Omega Solutions found weaknesses in the UK’s most popular refrigeration controllers, made by Resource Data Management (RDM), and Pen Test Partners verified them. The NCSC, Defra and the Food Standards Agency then worked with industry to take thousands of controllers off the open internet, in some cases by unplugging them and checking temperatures by hand (BBC News, 2026).

Ken Munro of Pen Test Partners said the controllers “had a similar weak password problem to the Danfoss and other controllers that were attacked so successfully”. RDM disputes how critical the flaws are, because exploiting them meant getting hold of the hardware. It says it has released its first patches and seen no sign of malicious activity.

The Cybersecurity and Infrastructure Security Agency (CISA), the FBI and other US agencies published joint guidance on 5th November on hardening refrigeration and cold chain monitoring systems (CISA, 2026). Chris Butera, CISA’s acting executive assistant director for cybersecurity, said every organisation relying on these systems “should assume it could be a target” (Infosecurity Magazine, 2026).

On 9 November, France formally attributed the October attacks on its supermarkets to Shahid Kaveh, a cyber unit of Iran’s Islamic Revolutionary Guard Corps (BleepingComputer, 2026). The attribution covers the October attacks in France only (Euronews, 2026).

Would the fixes have protected them?

France’s national cyber agency, ANSSI, says the October attacks exploited basic security failures. Its director, Vincent Strubel, told the French Senate on 21 October: “Our analysis is that basic security flaws were exploited” (our translation). He described controllers exposed directly to the internet with weak passwords, and dismissed claims that the researchers’ published flaws were used (Public Sénat, 2026). How the November wave got in hasn’t been confirmed (SentinelOne, 2026). The equipment itself is well documented.

In August 2026, Claroty’s Team82 presented research on the Danfoss AK-SM 800A and the Copeland XWEB Pro at DEF CON 34. It found three vulnerabilities in the Danfoss system manager and 23 in the Copeland platform, 21 of them rated high severity (Claroty Team82, 2026).

Both manufacturers had fixed these through coordinated disclosure before the research went public. Danfoss released AK-SM 800A firmware R4.3.1 in August 2025, and Copeland released XWEB Pro firmware 1.13 in February 2026 (Cooling Post, 2026). The CISA guidance still lists unpatched controllers as a route in (CISA, 2026), which suggests plenty of installed units never received those updates.

Separately, Midnight Blue researcher Carlo Meijer has found six more flaws in the AK-SM 800A that allow remote code execution without a login. As of 17 November there was no patch, and the researchers say firmware 5.4.0 doesn’t fix them (Security Affairs, 2026).

The fixes were out before the attacks beganTimeline from August 2025 to November 2026: Danfoss and Copeland firmware fixes, Claroty research published at DEF CON 34, the first wave in France, ANSSI pointing to exposed controllers with weak passwords, the second wave across Europe, then joint US guidance.THE TIMELINEThe fixes came before the attacksAUG 2025Danfoss fix releasedAK-SM 800A firmware R4.3.1 addresses the flaws Clarotylater published.FEB 2026Copeland fix releasedXWEB Pro firmware 1.13 patches 23 reportedvulnerabilities.AUG 2026Research made publicClaroty Team82 presents its findings at DEF CON 34.11-12 OCTFirst wave, FranceAround 700 supermarkets hit. CERT-FR names Danfoss andCopeland/Dixell controllers.21 OCTFrance's cyber agency reportsANSSI points to controllers exposed to the internet withweak passwords, not the published flaws.1-2 NOVSecond wave across EuropeChains in at least seven countries. UK meat processorsalso affected.5 NOVJoint US guidanceCISA, the FBI and partners urge operators to hardenrefrigeration systems.Sources: Cooling Post, Claroty Team82, CERT-FR, Public Sénat, CISA. Fix dates arevendor release dates, not installation dates. At the time of publishing (25 November2026), no official source had named the exact flaws used, or confirmed how theNovember wave got in.

Timeline from August 2025 to November 2026 showing the Danfoss and Copeland firmware fixes released before the October and November attacks on European supermarkets.

A fix on a vendor’s download page does nothing for a controller on a plant-room wall. 

How easily it gets there is decided at the design stage.

Four design decisions on the attack pathA simplified path from the internet to a freezer heating element, with four design decisions marked where they sat: a hidden service login, calculable admin passwords, an interface on the open internet and an update path nobody uses, plus the open question of an independent hardware limit.THE ATTACK PATHFour decisions on the attack pathThe internet1Hidden service loginBypasses the customer's owncredentials2Calculable admin passwordsWorked out from the date and theMAC address3On the open internetReachable from outside the siteWeb management interfaceWhere the operator andcontractor log in4An update path nobody usesFixes released, never installedon siteSupervisory controllerFor example Danfoss AK-SM orCopeland XWEBRS485 / Modbus field busField controllers?Independent hardware limitWhat stops the worst case if thefirmware is compromised?Heaters and fansPhysical outcomeCooling switched off orheating forced onSimplified. Weaknesses 1 to 4 are documented in published research and the CISA factsheet. At the time of publishing (25 November 2026), France's cyber agency had linkedthe October attacks to exposed controllers with weak passwords. No official sourcehad named the exact flaws used.

Four design decisions on the attack path

Products also outlive their software support. In our Futureproofing Manufacturing survey of 593 UK respondents, 88% said they run into obsolescence issues at least once a year (ByteSnap Design, 2025).

Authenticated updates that fall back to the last working image if they fail, plus a decision on what happens when support ends, belong in the specification from the start. Martin Thompson’s guide to designing firmware for secure OTA updates covers dual-bank layouts and recovering from a failed install.

Comparison of a site-visit update, which can stall at every step, with a designed-in update that is signed, checked, installed to a spare slot and falls back to the last working image if it fails.

Why patches never reach the plant roomTwo update paths compared. Update by site visit relies on a vendor notice, a contractor, a booked visit and a manual install, and can stall at every step. An update path designed in delivers a signed update over an authenticated channel, checks it, installs it to a spare slot and falls back to the last working image if it fails.THE UPDATE PATHA patch only protectsdevices that install itUPDATE BY SITE VISITVendor publishes a fixContractor hears about itSite visit is bookedEngineer updates on siteDowntime risk if it failsUPDATE DESIGNED INVendor signs the updateDelivered over anauthenticated channelDevice checks the signatureInstalls to a spare slotFalls back if it failsEach step is a chancefor the update to stallFewer people, fewer visits,a recoverable failureThe authenticated channel can run through a firewall or managed gateway, so thecontroller itself stays off the open internet, as CISA recommends.

Our own approach starts with secure boot and encrypted update files, and Linux-based systems also get a read-only root filesystem.

The device decrypts an update and writes it to a second partition, and the bootloader only loads it once verification succeeds. If that boot fails, the update is wiped and the device returns to its previous image.

Encrypting update files also slows down the kind of reverse-engineering shown in the published proofs of concept.

For more on the first step, see our series on secure boot for the i.MX6.

Should firmware be the only safeguard?

In Claroty’s demonstration, a compromised Copeland supervisor switched off the cooling fans on a field controller connected over Modbus, and the controller’s display carried on showing a normal temperature as the cabinet warmed (Claroty Team82, 2026).

CISA warns that attackers can also force units into continuous heating and defrost cycles (CISA, 2026). Once software drives heaters or compressors, a compromise can cause physical damage that the operator may not see on the display.

Hardware limits are harder to set than they sound. On a product that can heat as well as cool, there may be no single correct limit, and on a product used in many different ways, hardware protection probably cannot protect the food it holds.

A hardware limit can still stop the device destroying itself, and where a product has a critical control function, hardware lock-outs could prevent a catastrophic failure.

Where a controller can drive heating to dangerous levels, we would add a hardware lock-out on both maximum temperature and duration.

What will the Cyber Resilience Act expect from your product?

If you sell connected products into the EU, the Cyber Resilience Act (CRA) covers most of these weaknesses. Our EN 18031 and CRA preparation roadmap sets out the full timeline.

Since 11 September 2026, manufacturers have had to report actively exploited vulnerabilities, and that duty covers products already on the market, including controllers installed years ago (Article 69(3)).

From 11 December 2027, the main requirements apply, including secure default settings and security updates for a defined support period (Regulation (EU) 2024/2847). Those requirements cover products placed on the market from that date, and older products only if they’re substantially modified (Article 69(2)).

Products with a radio interface already have to meet the cybersecurity requirements of the Radio Equipment Directive, which became mandatory on 1 August 2025 (Delegated Regulation (EU) 2022/30).

The EN 18031 standards are the usual way to show compliance. Delegated Regulation (EU) 2026/339 repeals those RED requirements to avoid overlap with the CRA, which applies in full from 11 December 2027.

⏩ Does your product have a radio?

Our free EN 18031-1 compliance assessment tool gives a quick view of its compliance risk. A wired-only controller falls outside the RED, so EN 18031 doesn't apply to it, but it is still in scope of the CRA. The UK's PSTI rules cover consumer products, so they won't apply to most commercial controllers.

Five checks for your next design review

1. List every way into the product that doesn’t use the customer’s own credentials, including service and factory modes. Remove them or tie them to the customer’s login. Debug ports count too: our guide to securing embedded Linux IoT devices covers JTAG and UART.

2. Check how default passwords are generated. If anyone could derive one from the label or the firmware image, change the scheme.

3. Check what the device exposes by default on each network interface. An installer should have to switch remote access on deliberately.

4. Walk through a field update the way a contractor would, and count the steps. Decide what happens when support ends, including how you’ll track components heading for end of life.

5. Work out the worst physical outcome a compromised controller could cause, and what stops it. Check whether anyone would notice if the display showed a false reading.

Five checks for your next design reviewA five-point design review checklist from the 2026 European refrigeration controller attacks, covering service access, default credentials, network exposure, field updates and physical limits.DESIGN REVIEW CHECKLISTFive checks for your next design reviewLessons from the 2026 European refrigeration controller attacks1SERVICE ACCESSFind every way in that skips the customer's loginInclude service, factory and debug modes. Remove them or tie themto the customer's credentials.2CREDENTIALSMake default passwords impossible to deriveIf the label or firmware image gives one away, change the scheme.3NETWORK EXPOSUREShip with remote access switched offCheck what each interface exposes by default. Installers shouldturn remote access on deliberately.4FIELD UPDATESCount the steps in a field updateWalk it through as a contractor would, and decide what happenswhen support ends.5PHYSICAL LIMITSBound the worst physical outcomeKnow what a compromised controller could do, and what stops it.BYTESNAP DESIGN | BYTESNAP.COM

Get a second opinion on your product.

If you're responsible for a connected Linux-based product already in the field, our embedded Linux security management service filters CVE alerts to your device's configuration, then applies and tests targeted patches. Book a security audit with our engineers.

FAQs

Attackers got remote access to supervisory refrigeration controllers, mainly Danfoss AK-SM and AK-SC and Copeland/Dixell XWEB units, and changed their settings (CERT-FR, 2026). US guidance points to unpatched or internet-reachable controllers (CISA, 2026). France’s cyber agency says the October attacks relied on internet-exposed controllers and weak passwords, not the published flaws (Public Sénat, 2026). No official source has named the route used in November.

Some were. Claroty Team82 published flaws in the Danfoss AK-SM 800A and Copeland XWEB Pro in August 2026 (Claroty Team82, 2026). Both vendors had already released fixes: Danfoss in August 2025 and Copeland in February 2026 (Cooling Post, 2026). France’s cyber agency says the October attacks didn’t need those flaws, because exposed controllers with weak passwords were enough. Secure defaults matter as much as a usable update path.

France has formally attributed the October attacks on its supermarkets to Shahid Kaveh, a cyber unit of Iran’s Islamic Revolutionary Guard Corps (BleepingComputer, 2026). The attribution covers France only, and the November wave elsewhere in Europe remains unattributed. For product designers, the attacker matters less than the weaknesses, because anyone who finds them can exploit them.

Networked controllers placed on the EU market count as products with digital elements, so they fall within the CRA (Regulation (EU) 2024/2847). Vulnerability reporting has applied since September 2026, including for controllers already installed. The full requirements, including secure defaults and security updates, apply to products placed on the market from 11 December 2027. Check your product’s category, because some need third-party conformity assessment.

Start with the four design decisions on the attack path. Remove hidden service logins, make default passwords unique to each device, leave remote access off until an installer enables it, and make field updates easy enough that contractors actually apply them. Where a compromised controller could cause physical harm, consider a limit the firmware can’t override.

Nathan Padoin Software Engineer

Nathan Padoin has been an embedded software engineer at ByteSnap Design since 2013, after gaining his computer science degree at the University of Southampton.

He works on embedded systems projects, from control systems to multimedia devices, for industrial applications among others.

His expertise includes Linux and Android BSP development and embedded security, and he wrote ByteSnap Design’s series on secure boot for the i.MX6.

Share:

Related Posts

Testing components with multimeter on anti-static mat
background_1
PCB Design Requirements__
macro pcb